Difference between revisions of "VFDs"
From PROBOTIX :: wiki
Line 1: | Line 1: | ||
+ | To change settings: | ||
+ | 1. Press [PROGRAM] | ||
+ | 2. Use arrow keys to change to program number your looking to change | ||
+ | 3. Press [SET] | ||
+ | 4. Use the arrow keys to change the value to appropriate value | ||
+ | 5. Press [SET] to save the value | ||
+ | |||
+ | Setting needed for galaxy series machines: | ||
+ | |||
+ | PD001 – Source of Run Command – 0 | ||
+ | PD002 – Source of Operating Frequency – 1 | ||
+ | PD070 – Analog Input 0-10V – 0 | ||
+ | PD144 – Rated Motor Revolution – 3000 | ||
+ | |||
+ | Displaying RPM instead of Hz: | ||
+ | |||
+ | Press the arrow over key until the Rott light is illuminated | ||
[[File:VFD_wiring_diagram.jpg|thumb|500px|left|alt=VFD Wiring|VFD Wiring Diagram]] | [[File:VFD_wiring_diagram.jpg|thumb|500px|left|alt=VFD Wiring|VFD Wiring Diagram]] |
Revision as of 09:35, 31 August 2015
To change settings:
1. Press [PROGRAM] 2. Use arrow keys to change to program number your looking to change 3. Press [SET] 4. Use the arrow keys to change the value to appropriate value 5. Press [SET] to save the value
Setting needed for galaxy series machines:
PD001 – Source of Run Command – 0 PD002 – Source of Operating Frequency – 1 PD070 – Analog Input 0-10V – 0 PD144 – Rated Motor Revolution – 3000
Displaying RPM instead of Hz:
Press the arrow over key until the Rott light is illuminated